Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 7889 : 1997

Specifications

Voltage Rating : 1.5 mm2 to 630 mm2 – 600 / 1000V
Temperature Range : -15 °C to 90°C
Minimum Bending Radius
4.0 to 50 mm2 : 10 X Overall diameter.
70 & 630 mm2 : 12 X Overall diameter.
Test Voltage : 2 kV 15 min.
Cable Construction
Conductor
Plain annealed copper conductor : 4 mm2 to 630 mm2 stranded class 2 complying with BS EN 60228, HD 383, IEC 60228
Insulation : GP8 conforming to BS 7655-1.3 ( XLPE )
Sheath : Type 9 specified in BS 7655-4.2
Insulation Colour : Natural
Sheath Colour : Black

Cable Design Parameters