Conductor

Laid Up Cores

Bunched Conductor

Insulation

Armour

Petp Tape

Sheath



Conductor

Laid Up Cores

Bunched Conductor

Insulation

Armour

Petp Tape

Sheath
These cables are used for intrinsically safe circuits. For hazard prone areas cables with blue sheath are used for controlling and measuring requirements.
These installations are not earthed and require a seperate power circuit.
Tinned copper braid screen ensures disturbance free transmission of data and signals.
Adapted to DIN EN 60079-14: VDE 0165 Part 1.
Nominal Voltage : U / U 300 / 500V.
Insulation Resistance : Min. 20 GΩ x cm
Temperature Range : Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
Minimum Bending Radius : Flexing 20 x cable ø. Fixed installation 6 x cable ø
Test Voltage : 3000V
Mutual Capacitance:
core to core (approx.) – 140 nF/km
core to screen (approx.) – 185 nF/km
Inductance: 0.68 mH/km (approx.)
Core insulation of special PVC TI2 EN 50363-3.
Black core with continuous white numbering according to DIN VDE 0293.
Cores stranded in layers with optimal lay-length.
Plastic foil over the laid up cores.
Tinned-copper braided screen, approx. 85% coverage.
Outer sheath of special PVC, TM2 to DIN/BS EN 50363-4.1.
Colour Blue (RAL 5015).
PVC self-extinguishing and flame retardant according to IEC 60332-1-2.
Note :
X = Without green/yellow earth core (OZ)