Conductor

Insulation

Laid Up Cores

Heat Barrier

Drain Wire

Fire Barrier

Fire Barrier Covered

Sheath



Conductor

Insulation

Laid Up Cores

Heat Barrier

Drain Wire

Fire Barrier

Fire Barrier Covered

Sheath
These cables are used in high rise buildings, commercial complexes, schools and educational institutions, hospitals, etc. for the connection with security systems like smoke detectors, emergency lightings, exit signboards and fire command center. These cables are used where the fire safety is utmost important.
BS 7629, BS 50200.
Voltage Rating : 300/500V
Temperature Range : -30°C to + 70°C (The cable should not be flexed when either the ambient or cable temperature is below 0°C)
Minimum Bending Radius : 6D
FFX200 05mSOZ1-R – CU/MGT/SR/OSCR/LSZH 300/500V Class. 2.
Plain annealed copper conductor to Cl. 2, BS EN 60288.
Primary insulation of glass mica fire resistanttape.
Secondary insulation of highper for mance Silicone rubber.
EI2 to BS7655Section 1.1.
Core colours :
2 Core : blue, brown.
3 Core : blue, brown, black.
4 Core : blue, brown, black, grey.
Earth/Drain wire of annealed tinned copper to BS EN 60228.
Glass fiber tape.
Electrostatic screen of aluminium fire barrier with 125 % overlap.
Sheath type LTS3 to BS 7655 section 6.1.
Zero halogen, low smoke, flame retardant, abrasion resistant.
BS7629-1:2008-300/500V fire resistant electric cables corrosiveg as es when having low emission of smoke and affected by fire.
BS6387 specification for performance requirements for cables required to maintain circuit conditions.
Integrity under fire category CWZ cables resistant to fire, water spray mechanical shock.
Standard fire resistant cables as described in Clause 262 do fBS5839-1:2002 +A2:2008.
Fire detection and Fire alarm systems for buildings.
Class Ph120 when tested in accordance with BS EN 50200 – Method of test for resistance to fire of unprotected small cables for use in emergency circuits.
BS8434-2.
FFX200 05SOZ1-U – CU/SR/OSCR/LSZH 300/500V Class 1.
Plain annealed copper conductor Cl.1, to BS EN 60288.
Insulation of high performance Silicone rubber.
EI 2 to BS 7655 Section 1.1.
Core colours:
2 Core : blue, brown.
3 Core : blue, brown, black.
4 Core : blue, brown, black, grey.
Earth/Drain wire of annealed tinned copper Cl.1 to BS EN 60228.
Electrostatic screen of aluminium fire barrier with 125 % overlap.
Sheath Type LTS3 to BS 7655 section 6.1.
Zero halogen, low smoke, flame retardant, abrasion resistant.
BS 7629 -1 : 2008 – 300 / 500V fire resistant electric cables corrosive gases when having low emission of smoke and affected by fire.
BS 6387 specification for performance requirements for cables required to maintain circuit conditions.
Integrity under fire Category CWZ cables resistant to fire, water spray mechanical shock.
FFX200 05mZOZ1-R – CU/MGT/LS0H/OSCR/LS0H 300/500V Class 2.
Plain annealed copper conductor to BS EN 60288, class 2.
Primary insulation of glass mica fire resistant tape.
Secondary insulation to BS EN 50363-5, Type EI 5, Low smoke zero halogen (LSZH) cross-linkable flame retardant insulation.
Core colours:
2 Core : blue, brown.
3 Core : blue, brown, black.
4 Core : blue, brown, black, grey.
Glass fibre tape.
Earth/Drain wire of annealed tinned copper to BS EN 60228.
Electrostatic screen of aluminium fire barrier.
Sheath Type LTS3 to BS 7655 section 6.1.
*Low smoke zero halogen (LSOH), flame retardant.
BS 7629 -1, 300 / 500V fire resistant electric cables with non corrosive gases and low emission of smoke when affected by fire.
Category STANDARD 60 when tested in accordance with BS EN 50200-Method of test for resistance to fire of unprotected small cables for use in emergency circuits.
In addition, it shall meet the 30 min survival time when tested in accordance with BS EN 502000,Annex E.
Meets requirement for the fire resistant cables as described in clause 262d of BS 5839-1
FFX – Fire Alarm Cable,200 – 300/500V Multicore(Type),05 – 300/500V (Voltage),mS – Mica Tape + Silicon Rubber,
mZ – Mica Tape+ Thermosetting LS0H, S – Silicon Rubber,O – Overall Alluminium screen, z1 -LSZH
U Solid conductor to EN 60228 class 1, R – Stranded conductor to EN 60228 class 2